Multi-Function Power Meter

PA330

ÜberblickSpezifikationenBestellinformationenAnfrageRessourcen

PA330 is designed for single and three phase power monitoring and measurement. It provides wide range of measurements including current, voltage, energy, watt, power factor, watt-hour, frequency, etc. Moreover, PA330 includes built-in RS485 that easily integrates with most third SCADA system. DIN 96*96 standard compact size enable PA330 easily installed. The cost efficiency and wide flexibility
application also makes PA330 a good option for modern power monitoring.

Features

  • Comply IEC62053-22 Class 0.5 standard
  • V、I accuracy <0.2%, Wh<0.5%, with bi-directional true RMS energy measurement
  • More than 90 parameters measure
  • Current direction setting to correct the display value
  • Large size of LCD with backlight adjustment in 4-stage, easy to operate
  • Power Quality measurement in V/I THD、V/I unbalance、V Eligibility、Min.& Max. parameters
  • Compact size, standard DIN 96*96, equipped with four clips to tight the meter on the sheet metal
  • With RS485 communication protocol
  • Good accuracy, wh<0.5%(PF=1)

Mounting

Front View (mm) Back View (mm)

After mounting the instrument, place all four support latch in position.
Panel cut-out area is 92x92mm

Aux Power AC80 264V/DC100 300V, Max.2.3W
Input Current 2mA ~ 5A
V i nput burden ≥ 2MΩ (per channel), max 0.18VA
I input burden ≤ 5mΩ (per channel), max 0.125VA
Accuracy V、I 0.2% , W 0.5% (PF=1.0)
Frequency 45 ~ 65Hz
Measures V, I, kW, kvar, kVA, kWh, kvarh, kVAh, PF, Frequency, Demand, Running hour
Alarms NONE 、 OVER V/I 、 OVER F 、 UNDER V /I 、 UNDER F 、 OVER Dmd 、 ANY
Power Quality V/I THD : accumulate up to 54 orders, 5400/second s ampling rate
V/I unbalance 、 V Eligibility 、 Min.& Max. parameters
Display Mono 68X59 LCD
Communication RS485, Lon (option)
Timer RTC
Wiring Ports Aux Power 、 Voltage 、 Current 、 DO*2 、 RS485 、 LON
I/O DO OUTPUT*2 DO1 Alarm output 、 DO2 Pulse/ Alarm output
Operation Temperature -20 ~ 70 °C
Lagertemperatur -25 ~ 80 °C
Humidity 20 ~ 90% RH
Dust/Water Proof Rating Panel : IP52
Case : IP20
Abmessungen 96 x 96 x 97 mm (W x H x L)
Power consumption 0.45~0.7W (Backlight off)
1.3~1.7W (Max. ,Backlight)
2.3W (Max. Backlight & Lon module)
Environmental Conditions Indoor use
Altitude up to 2000M
Transient overvoltage on the mains supply is 2500V
Pollution degree : 2
Certificate 1. LVD Test : EN61010-1
2. CE Test
EN61326 Conducted Emission
EN61326 Radiated Emission
EN61000-3-2 Harmonic Current Emission
EN61000-3-3 Voltage Fluctuation and Flicker
EN61000-4-2 Electrostatic Discharge
EN61000-4-3 Radiated Susceptibility
EN61000-4-4 Electrical Fast Transient/Burst
EN61000-4-5 Surge
EN61000-4-6 Conducte d Susceptibility
EN61000-4-8 Power Frequency magnetic Field
EN61000-4-11 Voltage Dips and Interruption
3. FCC Test : Class A and CISPR 22

 

P/N Communication
PA330-0 RS485
PA330-1 Lon