Multi-Function Power Meter

PA330

OverviewSpecificationsOrdering InformationInquiryResources

PA330 is designed for single and three phase power monitoring and measurement. It provides wide range of measurements including current, voltage, energy, watt, power factor, watt-hour, frequency, etc. Moreover, PA330 includes built-in RS485 that easily integrates with most third SCADA system. DIN 96*96 standard compact size enable PA330 easily installed. The cost efficiency and wide flexibility
application also makes PA330 a good option for modern power monitoring.

Features

  • Comply IEC62053-22 Class 0.5 standard
  • V、I accuracy <0.2%, Wh<0.5%, with bi-directional true RMS energy measurement
  • More than 90 parameters measure
  • Current direction setting to correct the display value
  • Large size of LCD with backlight adjustment in 4-stage, easy to operate
  • Power Quality measurement in V/I THD、V/I unbalance、V Eligibility、Min.& Max. parameters
  • Compact size, standard DIN 96*96, equipped with four clips to tight the meter on the sheet metal
  • With RS485 communication protocol
  • Good accuracy, wh<0.5%(PF=1)

Mounting

Front View (mm) Back View (mm)

After mounting the instrument, place all four support latch in position.
Panel cut-out area is 92x92mm

Aux Power AC80 264V/DC100 300V, Max.2.3W
Input Current 2mA ~ 5A
V i nput burden ≥ 2MΩ (per channel), max 0.18VA
I input burden ≤ 5mΩ (per channel), max 0.125VA
Accuracy V、I 0.2% , W 0.5% (PF=1.0)
Frequency 45 ~ 65Hz
Measures V, I, kW, kvar, kVA, kWh, kvarh, kVAh, PF, Frequency, Demand, Running hour
Alarms NONE 、 OVER V/I 、 OVER F 、 UNDER V /I 、 UNDER F 、 OVER Dmd 、 ANY
Power Quality V/I THD : accumulate up to 54 orders, 5400/second s ampling rate
V/I unbalance 、 V Eligibility 、 Min.& Max. parameters
Display Mono 68X59 LCD
Communication RS485, Lon (option)
Timer RTC
Wiring Ports Aux Power 、 Voltage 、 Current 、 DO*2 、 RS485 、 LON
I/O DO OUTPUT*2 DO1 Alarm output 、 DO2 Pulse/ Alarm output
Operation Temperature -20 ~ 70 °C
Storage Temperature -25 ~ 80 °C
Humidity 20 ~ 90% RH
Dust/Water Proof Rating Panel : IP52
Case : IP20
Dimension 96 x 96 x 97 mm (W x H x L)
Power consumption 0.45~0.7W (Backlight off)
1.3~1.7W (Max. ,Backlight)
2.3W (Max. Backlight & Lon module)
Environmental Conditions Indoor use
Altitude up to 2000M
Transient overvoltage on the mains supply is 2500V
Pollution degree : 2
Certificate 1. LVD Test : EN61010-1
2. CE Test
EN61326 Conducted Emission
EN61326 Radiated Emission
EN61000-3-2 Harmonic Current Emission
EN61000-3-3 Voltage Fluctuation and Flicker
EN61000-4-2 Electrostatic Discharge
EN61000-4-3 Radiated Susceptibility
EN61000-4-4 Electrical Fast Transient/Burst
EN61000-4-5 Surge
EN61000-4-6 Conducte d Susceptibility
EN61000-4-8 Power Frequency magnetic Field
EN61000-4-11 Voltage Dips and Interruption
3. FCC Test : Class A and CISPR 22

 

P/N Communication
PA330-0 RS485
PA330-1 Lon